由于出现"电源故障"错误、节点重新启动
适用场景
- AFF FAS8200或 FAS2620 / FAS2650
 - FAS2720/FAS2750
 - AF-A220
 
问题描述
- Node console或
SP/BMC> system log或 输出显示节点因"Power Fail"(电源故障)错误而重新启动。 
示例 (重新启动):
****************************
 * Power Fail - Please Wait *
 ****************************
 ...
 Destage is in progress, please wait
 ..........................................
 Destage is completed successfully
 Powering off from the backup power source
 :
 Waiting for giveback...(Press Ctrl-C to abort wait)
示例 (启动循环):
****************************
 * Power Fail - Please Wait *
 ****************************
 ...
 Destage is in progress, please wait
 ..........................................
 Destage is completed successfully
 Powering off from the backup power source
 BIOS Version: 11.2.1
 Portions Copyright (C) 2014-2018 NetApp, Inc. All Rights Reserved.
 ...
 Initializing System Memory ...
 Loading Device Drivers ...
 BIOS Version: 11.2.1
 Portions Copyright (C) 2014-2018 NetApp, Inc. All Rights Reserved.
 Initializing System Memory ...
 Loading Device Drivers ...
- 节点 
SP/BMC events all报告: 
Record 1234: Mon Jan  1 00:01:01 2024 [SP.emergency]: System input power lost
 Record 2345: Mon Jan  1 00:10:10 2024 [SP.emergency]: System input power lost
- 任何电源设备(PSU)、配电设备(PDU) 或任何其他数据中心电气 元件(磁盘架、交换机等)均不报告任何其他电源警报