由于出现"电源故障"错误、节点重新启动
适用场景
- 运行 服务处理器固件5.11P1的AFF A300/FAS8200或FAS2620/FAS2650。
- FAS2720/FAS2750
问题描述
- 节点控制台或
SP/BMC> system log
输出显示节点因"电源故障"错误而重新启动。
示例 (重新启动):
****************************
* Power Fail - Please Wait *
****************************
...
Destage is in progress, please wait
..........................................
Destage is completed successfully
Powering off from the backup power source
:
Waiting for giveback...(Press Ctrl-C to abort wait)
示例 (启动循环):
****************************
* Power Fail - Please Wait *
****************************
...
Destage is in progress, please wait
..........................................
Destage is completed successfully
Powering off from the backup power source
BIOS Version: 11.2.1
Portions Copyright (C) 2014-2018 NetApp, Inc. All Rights Reserved.
...
Initializing System Memory ...
Loading Device Drivers ...
BIOS Version: 11.2.1
Portions Copyright (C) 2014-2018 NetApp, Inc. All Rights Reserved.
Initializing System Memory ...
Loading Device Drivers ...
- 节点
SP/BMC events all
报告:
Record 1234: Mon Jan 1 00:01:01 2024 [SP.emergency]: System input power lost
Record 2345: Mon Jan 1 00:10:10 2024 [SP.emergency]: System input power lost
- 任何电源设备(PSU)、配电设备(PDU) 或任何其他数据中心电气 元件(磁盘架、交换机等)均未报告任何其他电源警报