由于电源故障、Brocade交换机状态从"运行状况良好"更改为"严重"
适用场景
问题描述
- 交换机状态已从"运行状况良好"更改为"严重"。
psshow
输出显示电源1出现故障。
psshow -v :
Power Supply #1 is faulty
Power Supply #2 is OK
sensorshow
输出显示sensor10(power supply)
有故障。
sensorshow :
sensor 1: (Temperature) is Ok, value is 33 C
sensor 2: (Temperature) is Ok, value is 41 C
sensor 3: (Temperature) is Ok, value is 37 C
sensor 4: (Temperature) is Ok, value is 36 C
sensor 5: (Temperature) is Ok, value is 37 C
sensor 6: (Temperature) is Ok, value is 32 C
sensor 7: (Temperature) is Ok, value is 56 C
sensor 8: (Fan ) is Ok,speed is 8141 RPM
sensor 9: (Fan ) is Ok,speed is 8043 RPM
sensor 10: (Power Supply) is Faulty
sensor 11: (Power Supply) is Ok
errdump
输出显示了报告的以下电源错误。
2023/09/17-04:27:09, [EM-1034], 403, CHASSIS, ERROR, BrocadeG620, PS 1 set to faulty, rc=2000e.
2023/09/17-04:28:00, [MAPS-1021], 404, FID 128, WARNING, NSWNT-DC-B, RuleName=defCHASSISBAD_PWR_CRIT, Condition=CHASSIS(BAD_PWR>=1), Obj:Chassis [ BAD_PWR,1] has contributed to switch status CRITICAL.
2023/09/17-04:28:00, [MAPS-1020], 405, FID 128, WARNING, NSWNT-DC-B, Switch wide status has changed from HEALTHY to CRITICAL.