FAS2650、FAS8200、AFF A200、AFF A300和AFF A800系统偶尔会报告EMS消息"nvme.bacy.wrongCharge "几秒钟、然后恢复
适用场景
- FAS2650/FAS2620
- FAS2720/FAS2750
- AFF A300/FAS8200
- AFF A200
- AFF A220
- AFF C190
- AFF A800
问题描述
nvmem.battery.wrongCharge
触发EMS消息后、电池将在几秒钟后恢复。
cluster::> event log show -severity * -event *battery*
[hostname: env_mgr: nvmem.battery.wrongCharge:alert]: The NVMEM battery charger is charging the battery even though the battery is not requesting to be charged. To prevent data loss, the system will shut down in 24 hours.
[hostname: env_mgr: nvmem.battery.normalCharge:notice]: The NVMEM battery charging status is normal.
system node environment sensors show
报告电池电量正常。
Bat Present PRESENT
Bat Temp normal 29 C 0 C 5 C 60 C 75 C
Bat Volt normal 8100 mV 5500 mV 5600 mV 8500 mV 8600 mV
Bat Pct Capacity normal 96 % 39 % 44 % -- --
Bat Curr normal 0 mA -- -- 1200 mA 1520 mA
Bat Rem Cap normal 1536 mA*hr -- -- -- --
Bat Full Cap normal 1536 mA*hr -- -- -- --
Bat Charge Curr normal 0 mA -- -- 2200 mA 2300 mA
Bat Charging State IDLE
Bat Charge Volt normal 8200 mV -- -- 8900 mV 9000 mV
Bat Initial FCC normal 1600 mA*hr -- -- -- --
Bat Dstg Cycles normal 26 cycles 2 cycles 5 cycles -- --
Bat Power Fault GOOD
Bat Dcharge FET ON
Bat Charge FET ON
Bat Cycle Count normal 15 cycles -- -- -- --
Bat Learning Active OFF
Bat Pack Invalid OK