RTC电池故障
适用于
- FAS/AFF 平台
- 实时时钟 (RTC) 纽扣电池
问题描述
- 节点和机箱故障指示灯亮起,出现以下错误:
hsamcmd --fault-show-all
===============================
tag origin fld fault reason count time
---- ------- ---- ------------- ------ -----
1 bmc /chassis-1/controller-a P3V3_BATT: Voltage Sensor 26 LNC 1 Wed Jun 25 10:58:10 2025
2 bmc /chassis-1/controller-a P3V3_BATT: Voltage Sensor 26 LCR 1 Wed Jun 25 10:58:22 2025
- 或者,节点和机箱故障 LED 点亮,但没有明确的故障指示
- 以下 EMS 消息,并将针对电池报告非关键故障:
Tue Sep 4 15:05:29 CEST [NODE1:monitor.chassisPower.degraded:warning]: Chassis power is degraded: RTC Battery is in WARN LOW state current voltage is 2774 mV, normal low is 2800 mV
SP-LATEST-IPMI
log showsP3.3V Batt
为以下条件。
P3.3V Batt warnlow 2660 mV 2537 mV 2695 mV 3307 mV 3447 mV
或
P3.3V Batt critlow 945 mV 2100 mV 2205 mV 3395 mV 3500 mV
SP-LATEST-SYSLOG
日志显示rtcWarnLowPower
BMC env_mgr[1534]: Payload EMS: EMS_monitor_rtcWarnLowPower(2660 mV)
- BMC
events all
显示P3.3V Batt is critical low
。
BMC env_mgr[1461]: P3.3V Batt is critical low
- 从 BMC/SP 显示
P3V_BAT
是以下条件:
Sensor Name | Current | Unit | Status | LCR | LNC | UNC | UCR
-----------------+------------+------------+------------+-----------+-----------+-----------+-----------
P3V_BATT | 2.840 | Volts | nc | 2.720 | 2.880 | 3.300 | 3.460
Or
P3V3_BATT | 0.963 | Volts | cr | 2.100 | 2.205 | 3.395 | 3.500