由于 PSU 故障,PDU 断路器已跳闸
适用于
- 电源分配单元 (PDU)
- 电源供应单元 (PSU)
- FAS8200
- DS224-12 磁盘机柜
- 具有冗余 PDU 和磁盘机柜电源的环境
- Cisco Nexus 3132Q-V
问题
- 为 NetApp 磁盘架和控制器供电的 PDU 断路器意外跳闸。
- 受影响的设备包括多个磁盘架电源和控制器。
- 磁盘架诊断的日志输出显示:
PowerSupplies:Element Status Status Bytes Status Descriptions1: OK 01,00,00,20 RQSTEDON2: CRITICAL 02,00,00,F3 DCFAIL, ACFAIL, OFF, RQSTEDON, FAIL
- 连接到同一 PDU 的 FC 交换机(3132Q-V)上也会显示电源错误。
2025 Mar 10 02:35:07 switch-01 %PLATFORM-2-PS_DETECT: Power supply 1 detected but shutdown (Serial number LXX12345XC)
2025 Mar 10 02:35:07 switch-01 %PLATFORM-5-PS_STATUS: PowerSupply 1 current-status is PS_SHUT
2025 Mar 10 02:35:07 switch-01 %PLATFORM-2-PS_CAPACITY_CHANGE: Power supply PS1 changed its capacity. possibly due to On/Off or power cable removal/insertion (Serial number LXX12345XC)
2025 Mar 10 02:35:07 switch-01 %PLATFORM-2-PS_RED_MODE_CHG: Power supply operational redundancy mode changed to non-redundant