在 AFF 上执行诊断测试期间,风扇 1 和 7 出现故障 A800
适用于
- AFF A800
问题
在 AFF A800[1]上从 boot_diags 运行诊断时,风扇 1 和 7 显示为 Failed 。 输出类似于以下内容:
============================================================
Fan Test:
============================================================
Set all fan to 60% Duty cycle
23000 * 60% = 13800
Check RPM in the range from 12420 to 15180 RPM
FAN_1 expect In range from 12420 to 15180 RPM, current 13648 RPM, result: pass
FAN_2 expect In range from 12420 to 15180 RPM, current 13573 RPM, result: pass
FAN_3 expect In range from 12420 to 15180 RPM, current 13501 RPM, result: pass
FAN_4 expect In range from 12420 to 15180 RPM, current 13604 RPM, result: pass
FAN_5 expect In range from 12420 to 15180 RPM, current 13602 RPM, result: pass
FAN_6 expect In range from 12420 to 15180 RPM, current 13575 RPM, result: pass
FAN_7 expect In range from 12420 to 15180 RPM, current 13607 RPM, result: pass
FAN_8 expect In range from 12420 to 15180 RPM, current 13482 RPM, result: pass
FAN_9 expect In range from 12420 to 15180 RPM, current 13548 RPM, result: pass
FAN_10 expect In range from 12420 to 15180 RPM, current 13657 RPM, result: pass
Set all fan to 80% Duty cycle
23000 * 80% = 18400
Check RPM in the range from 16560 to 20240 RPM
FAN_1 expect In range from 16560 to 20240 RPM, current 13641 RPM, result: fail
FAN_2 expect In range from 16560 to 20240 RPM, current 18021 RPM, result: pass
FAN_3 expect In range from 16560 to 20240 RPM, current 18192 RPM, result: pass
FAN_4 expect In range from 16560 to 20240 RPM, current 18179 RPM, result: pass
FAN_5 expect In range from 16560 to 20240 RPM, current 18063 RPM, result: pass
FAN_6 expect In range from 16560 to 20240 RPM, current 18161 RPM, result: pass
FAN_7 expect In range from 16560 to 20240 RPM, current 13591 RPM, result: fail
FAN_8 expect In range from 16560 to 20240 RPM, current 18009 RPM, result: pass
FAN_9 expect In range from 16560 to 20240 RPM, current 18103 RPM, result: pass
FAN_10 expect In range from 16560 to 20240 RPM, current 18036 RPM, result: pass
Load default fan table
RESULT: FAILED
System Test Summary:
CPU : PASSED
TPM : PASSED
Eth : PASSED
BMC : PASSED
PSU : PASSED
PCH-I2C : PASSED
RTC : PASSED
Quad Port 10GbE NIC Slot 4 : PASSED
Quad Port 10GbE NIC Slot 5 : PASSED
Mezzanine Dual Port 100GbE NIC : PASSED
FAN : FAILED
如果将 " 故障 " 风扇更换为正常运行的风扇,然后重新测试,则仍会显示风扇 1 和 7 出现故障。