In response to the recent rise in cyber threat due to the Russian-Ukraine crisis, NetApp is actively monitoring the global security intelligence and updating our cybersecurity measures. We follow U.S. Federal Government guidance and remain on high alert. Customers are encouraged to monitor the Cybersecurity and Infrastructure Security (CISA) website for new information as it develops and remain on high alert.

节点已关闭、但出现错误monitor.shutdown.chassisOverTemp:critical "Chassis temperature is too hot:system will be shutdown in 2 minutes"

Views:
38
Visibility:
Public
Votes:
0
Category:
fas-systems
Specialty:
hw
Last Updated:

状态信息

适用场景

  • AFF
  • FAS

问题描述

  • FAS 节点已关闭。
  • 在通过AutoSupport 关闭之前观察到的错误可能包括:

SHELF OVER TEMPERATURE
CHASSIS OVER TEMPERATURE
CHASSIS OVER TEMPERATURE SHUTDOWN

  • 在EMS日志中、在关闭之前观察到的错误可能包括类似于以下内容的错误:

[FAS-01: dsa_worker3: callhome.shlf.overtemp:error]: Call home for SHELF OVER TEMPERATURE 43 C (109 F)
[FAS-01: dsa_worker3: ses.status.temperatureError:critical]: DS4246 (S/N SHJMS000000011A) shelf 0 on channel 0a temperature error for Temperature sensor 1: critical status; overtemperature failure. Current temperature: 43 C (109 F). This module is on the front of the shelf on the left, on the OPS panel.

[FAS-01: env_mgr: monitor.chassisTemperature.warm:alert]: Chassis temperature is too warm: In Flow Temp is warning high (53 C).
[FAS-01: env_mgr: callhome.chassis.hitemp:error]: Call home for CHASSIS OVER TEMPERATURE

[FAS-01: dsa_worker4: ses.status.temperatureWarning:warning]: DS4246 (S/N SHJMS000000011A) shelf 0 on channel 0a temperature warning for Temperature sensor 3: non-critical status; overtemperature warning. Current temperature: 51 C (123 F). This module is on the rear of the shelf on the upper left power supply.
[FAS-01: power_low_monitor: monitor.chassisPower.degraded:warning]: Chassis power is degraded: Power Supply Status Critical.
[FAS-01: power_low_monitor: callhome.chassis.power:error]: Call home for CHASSIS POWER DEGRADED: Power Supply Status Critical.
[FAS-01: monitor: monitor.globalStatus.critical:critical]: Power Supply Status Critical. Chassis temperature is too high. Disk shelf fault. 

[FAS-01: env_mgr: monitor.shutdown.chassisOverTemp:critical]: Chassis temperature is too hot: System will be shutdown in 2 minutes
[FAS-01: env_mgr: callhome.chassis.overtemp:EMERGENCY]: Call home for CHASSIS OVER TEMPERATURE SHUTDOWN

 

Scan to view the article on your device
CUSTOMER EXCLUSIVE CONTENT

Registered NetApp customers get unlimited access to our dynamic Knowledge Base.

New authoritative content is published and updated each day by our team of experts.

Current Customer or Partner?

Sign In for unlimited access

New to NetApp?

Learn more about our award-winning Support