电源故障警报—AutoSupport 消息

Views:
86
Visibility:
Public
Votes:
0
Category:
data-ontap-7
Specialty:
hw
Last Updated:

适用场景

  • Data ONTAP 7 及更早版本
  • ONTAP 8
  • ONTAP 9

事件摘要

以下消息表示以下情况之一:

  • 电源已关闭或拔出。
  • 数据中心或配电单元(PDU)的电源出现故障或波动。
  • 磁盘架电源出现故障。
  • 电源线出现故障
  • 断路器已跳闸、并且已恢复供电。

系统日志消息指示存在上述哪种情况。电源(2)在磁盘架中是冗余的。

Shelf fault SHLFLT: System Notification from Filer1 (SHELF POWER INTERRUPTED) WARNING
AutoSupport PWRFLT:System Notification from Filer1 (SHELF POWER INTERRUPTED) WARNING
 

[ses.status.psWarning:warning]: DS14-Mk2-AT shelf 1 on channel 2a power warning for Power supply 2: non-critical status; DC undervoltage fault. This module is on the rear side of the shelf, at the right.       
[ses.status.psError:CRITICAL]: DS14-Mk2-AT shelf 1 on channel 2a power error for Power supply 2: critical status; power supply failed. This module is on the rear side of the shelf, at the right.

AutoSupport message: Shelf Power Interrupted

您可能还会看到以下AutoSupport 消息:

  SHELF_FAULT
  SHELF COOLING UNIT FAILED
  FAN FAIL

验证

验证哪个磁盘架报告错误。此错误消息指示磁盘架ID和通道、但在查找出现错误的组件时、此操作可能不有用。要使用问题描述 检查组件、请运行 environment status 命令、此命令将打印每个磁盘架的完整状态。

NetApp-01::> system node run -node Netapp-01A
Channel: 2a
        Shelf: 1
        SES device path: local access: 2a.18
        Module type: AT-FCX; monitoring is active
        Shelf status: critical condition
        SES Configuration, via loop id 79 in shelf 5:
        logical identifier=0x50050cc00219fae3
        vendor identification=XYRATEX 
        product identification=DS14-Mk2-AT
        product revision level=3737
        Vendor-specific information:
        Product Serial Number: OPSxxxxxxxxxxxx
        Optional Settings: 0x00
        Status reads attempted: 1336282; failed: 0
        Control writes attempted: 9756; failed: 0
        Shelf bays with disk devices installed:
        13, 12, 11, 10, 9, 8, 7, 6, 5, 4, 3, 2, 1, 0
        with error: none
        Power Supply installed element list: 1, 2; with error: 2
        Power Supply information by element:
        [1] Serial number: PMCxxxxxxxxxxxx
        Type: 5c
        Firmware version: <N/A>
        [2] Serial number: PMCxxxxxxxxxxxx
        Type: 5c
        Firmware version: <N/A>
        Cooling Unit installed element list: 1, 2; with error: none
        Temperature Sensor installed element list: 1, 2, 3; with error: none
        Shelf temperatures by element:
        [1] 22 C (71 F) (ambient) Normal temperature range
        [2] 42 C (107 F) Normal temperature range
        [3] 38 C (100 F) Normal temperature range
        Temperature thresholds by element:
        [1] High critical: 50 C (122 F); high warning 40 C (104 F)
        Low critical: 0C (32 F); low warning 10 C (50 F)
        [2] High critical: 63 C (145 F); high warning 53 C (127 F)
        Low critical: 0C (32 F); low warning 10 C (50 F)
        [3] High critical: 63 C (145 F); high warning 53 C (127 F)
        Low critical: 0C (32 F); low warning 10 C (50 F)
        ES Electronics installed element list: 1, 2; with error: none
        ES Electronics reporting element: 1
        ES Electronics information by element:
        [1] Serial number: IMSxxxxxxxxxxxx
        CPLD version: 24
        [2] Serial number: IMSxxxxxxxxxxxx
        CPLD version: 24

 

解决方法

  • 验证哪个磁盘架报告错误。此错误消息指示磁盘架ID和通道、但在查找出现错误的组件时、此操作可能不有用。要使用问题描述 检查组件、请运行 environment status 命令、此命令将打印每个磁盘架的完整状态。
  • 检查站点是否存在电源问题。
  • 使用已知正常工作的缆线检查电源线。
  • 检查两个风扇是否都在转动。如果一个风扇转速较慢、则可能表示电源出现故障。
  • 检查电源是否正常工作;红色指示灯应亮起。如果磁盘架电源发生故障、则可能需要更换。如果您需要更换架电源、请联系 NetApp技术支持 或使用NetApp 支持 站点请求更换。

 

Sign in to view the entire content of this KB article.

New to NetApp?

Learn more about our award-winning Support

NetApp provides no representations or warranties regarding the accuracy or reliability or serviceability of any information or recommendations provided in this publication or with respect to any results that may be obtained by the use of the information or observance of any recommendations provided herein. The information in this document is distributed AS IS and the use of this information or the implementation of any recommendations or techniques herein is a customer's responsibility and depends on the customer's ability to evaluate and integrate them into the customer's operational environment. This document and the information contained herein may be used solely in connection with the NetApp products discussed in this document.